Fresh air could save millions in data centre cooling costs, Intel has claimed, after a successful experiment in the New Mexico desert.
Replacing air conditioning by piping in outside air saved power costs with no appreciable increase in server failure rates, the company concluded in a research paper. Despite a lot of dust and major temperature changes - both long considered undesirable in data centres - the equipment wasn't affected, said Intel.
Green IT from A to Z
Click on the links below to find out more...
A is for Abroad
B is for Blades
C is for Carbon footprint
D is for Data centres
E is for Energy sources
F is for Freecycle
G is for Government
H is for Homeworking
I is for Ice caps
J is for Jobs (Steve)
K is for Kilowatts
L is for Landfill
M is for Mercury
N is for Nanogeneration
O is for Offsetting
P is for Paperless office
Q is for Queen
R is for Recycling
S is for SmartPlanet.com
T is for Travel
U is for Upgrade
V is for Virtualisation
W is for WEEE
X is for Xmas
Y is for You
Z is for Zero emissions
The paper said: "Servers...were subjected to considerable variation in temperature and humidity, as well as poor air quality; however, there was no significant increase in server failures. If subsequent investigation confirms these promising results, we anticipate using this approach in future, high-density data centres."
Intel estimated an annual cost reduction of approximately $143,000 for a small, 500kW data centre, based on electricity costs of eight cents per kWh. In a larger 10MW data centre, the estimated annual cost reduction was $2.87m.
Intel used a normal air filter that took larger particles out of the air but not fine dust. While the 32 servers and racks became coated in dust, and humidity was monitored but not controlled, the failure rate was 4.46 per cent, compared with a 3.83 per cent failure rate in Intel's main data centre over the same period.
The experiment was run for 10 months, between October 2007 and August 2008. Server units with more than 900 blades, used for production design, were split into two compartments. One of the compartments was air cooled, with temperatures ranging from 18 to 32°C. The other compartment was cooled using air conditioning, and used as a control.
Intel set up the experiment to challenge assumptions about optimal operating conditions in data centres. Received wisdom has it that temperature, humidity and air quality must be strictly maintained.
However, Intel set out with the premise that, as servers are designed for optimal performance in temperatures of up to 37°C, using air cooling in desert regions could be feasible.
The experiment was run as part of the Intel IT's Eight-Year Data Center Efficiency Strategy programme, which aims to reduce data centre costs.
Original article: Intel: Fresh air is good for datacentres from ZDNet UK
Deploy new infrastructure as required to meet business requirements.d) Ensuring high levels of technical quality and consistency for installation, ...
Area Sales Manager / Sales Engineer - Air Conditioning / HVAC Looking to join a rapidly expansive company? The Candidate You must have several years ...
Solution Architect required by international computer sevices company to consult with customers on a predominately pre-sales basis with the objective ...
Agenda Setters 2009
Welcome to the ninth annual Agenda Setters poll – silicon.com's list of the top 50 most influential individuals in the technology and IT industries, from techies and CIOs to entrepreneurs and business leaders. Find out more in our latest special report.
Stories from the web...
Copyright © 2008 CBS Interactive Limited. All rights reserved. Top of page
Bethan Jones Can I use a netbook as my everyday work machine? Part II silicon.com sub editor reveals whether her netbook delivered
Seb Janacek Magic Mouse - Apple's best ever? Minority Report: After years of disappointment, one Mac lover has hope